MedElevator Войти в исследования
← Поиск публикаций

DOI 10.1111/jam.12404

Медицинская библиотека · Journal of applied microbiology · 2013

Fumigation of a laboratory-scale HVAC system with hydrogen peroxide for decontamination following a biological contamination incident.

Meyer K M, Calfee M W, Wood J P, Mickelsen L, Attwood B, Clayton M, Touati A, Delafield R

СтатьяПоддержка исследования: вне правительства СШАПоддержка правительства СШАПеревод в очереди

Аннотация

AIMS: To evaluate hydrogen peroxide vapour (H2 O2 ) for its ability to inactivate Bacillus spores within a laboratory-scale heating, ventilation and air-conditioning (HVAC) duct system.

METHODS AND

RESULTS

Experiments were conducted in a closed-loop duct system, constructed of either internally lined or unlined galvanized metal. Bacterial spores were aerosol-deposited onto 18-mm-diameter test material coupons and strategically placed at several locations within the duct environment. Various concentrations of H2 O2 and exposure times were evaluated to determine the sporicidal efficacy and minimum exposure needed for decontamination. For the unlined duct, high variability was observed in the recovery of spores between sample locations, likely due to complex, unpredictable flow patterns within the ducts. In comparison, the lined duct exhibited a significant desorption of the H2 O2 following the fumigant dwell period and thus resulted in complete decontamination at all sampling locations.

CONCLUSIONS

These findings suggest that decontamination of Bacillus spore-contaminated unlined HVAC ducts by hydrogen peroxide fumigation may require more stringent conditions (higher concentrations, longer dwell duration) than internally insulated ductwork.

SIGNIFICANCE AND IMPACT OF THE STUDY: These data may help emergency responders when developing remediation plans during building decontamination.

Для цитирования: Meyer K M, Calfee M W, Wood J P, Mickelsen L, Attwood B, Clayton M, Touati A, Delafield R. Fumigation of a laboratory-scale HVAC system with hydrogen peroxide for decontamination following a biological contamination incident.. Journal of applied microbiology. 2013. DOI: 10.1111/jam.12404.

Предметные рубрики MeSH

Подготовка и перевод публикации
Обработка статьи · этапы, ошибки и управление
Загрузка состояния…

История · было → стало

Состояние обновляется каждые 5 секунд, пока блок открыт. Процент показывается только там, где известен объём работы. Пауза останавливает продолжение этапа; текущий запрос к источнику может завершиться.

Тип публикации указан по данным источника. Уровень доказательности автоматически не присваивается.