DOI 10.1111/j.1365-2672.2008.04044.x

Медицинская библиотека · Journal of applied microbiology · 2009

The efficacy of biocides and other chemical additives in cooling water systems in the control of amoebae.

Critchley M, Bentham R

СтатьяПоддержка исследования: вне правительства СШАПеревод в очереди

Аннотация

AIMS: In vitro experiments were undertaken to evaluate biocide formulations commonly used in cooling water systems against protozoa previously isolated from cooling towers. The investigations evaluated the efficacy of these formulations against amoebic cysts and trophozoites.

METHODS AND

RESULTS

Laboratory challenges against protozoa isolated from cooling towers using chlorine, bromine and isothiazolinone biocides showed that all were effective after 4 h. The presence of molybdate and organic phosphates resulted in longer kill times for bromine and isothiazolinones. All treatments resulted in no detectable viable protozoa after 4 h of exposure.

CONCLUSIONS

The chemical disinfection of planktonic protozoa in cooling water systems is strongly influenced by the residence time of the formulation and less so by its active constituent. Bromine and isothiazolinone formulations may require higher dosage of concentrations than currently practiced if used in conjunction with molybdate- and phosphate-based scale/corrosion inhibitors.

SIGNIFICANCE AND IMPACT OF THE STUDY: Cooling water systems are complex microbial ecosystems in which predator-prey relationships play a key role in the dissemination of Legionella. This study demonstrated that at recommended dosing concentrations, biocides had species-specific effects on environmental isolates of amoebae that may act as reservoirs for Legionella multiplication in cooling water systems.

Для цитирования: Critchley M, Bentham R. The efficacy of biocides and other chemical additives in cooling water systems in the control of amoebae.. Journal of applied microbiology. 2009. DOI: 10.1111/j.1365-2672.2008.04044.x.

Предметные рубрики MeSH

Подготовка и перевод публикации
Обработка статьи · этапы, ошибки и управление
Загрузка состояния…

История · было → стало

Состояние обновляется каждые 5 секунд, пока блок открыт. Процент показывается только там, где известен объём работы. Пауза останавливает продолжение этапа; текущий запрос к источнику может завершиться.

Тип публикации указан по данным источника. Уровень доказательности автоматически не присваивается.