DOI 10.1016/j.ajic.2021.02.013
Hospital-acquired Legionella pneumonia outbreak at an academic medical center: Lessons learned.
Аннотация
BACKGROUND
An outbreak of Legionella pneumonia occurred at a university hospital using copper-silver ionization for potable water disinfection. We present the epidemiological and laboratory investigation of the outbreak, and associated case-control study.
METHODS
Cases were defined by syndrome compatible with Legionella pneumonia with laboratory-confirmed Legionella infection. The water circuit and disinfection system were assessed, and water samples collected for Legionella culture. Whole genome multi-locus sequence typing (wgMLST) was used to compare the genetic similarity of patient and environmental isolates. A case-control study was conducted to identify risk factors for Legionella pneumonia.
RESULTS
We identified 13 cases of hospital-acquired Legionella. wgMLST revealed >99.9% shared allele content among strains isolated from clinical and water samples. Smoking (P= .008), steroid use (P= .007), and documented shower during hospitalization (P= .03) were risk factors for Legionella pneumonia on multivariable analysis. Environmental assessment identified modifications to the hospital water system had occurred in the month preceding the outbreak. Multiple mitigation efforts and application of point of use water filters stopped the outbreak.
CONCLUSIONS
Potable water system Legionella colonization occurs despite existing copper-silver ionization systems, particularly after structural disruptions. Multidisciplinary collaboration and direct monitoring for Legionella are important for outbreak prevention. Showering is a modifiable risk factor for nosocomial Legionella pneumonia. Shower restriction and point-of-use filters merit consideration during an outbreak.
Предметные рубрики MeSH
Подготовка и перевод публикации
Обработка статьи · этапы, ошибки и управление
Ошибки и ограничения
История · было → стало
Состояние обновляется каждые 5 секунд, пока блок открыт. Процент показывается только там, где известен объём работы. Пауза останавливает продолжение этапа; текущий запрос к источнику может завершиться.
Тип публикации указан по данным источника. Уровень доказательности автоматически не присваивается.