DOI 10.1016/j.ijid.2020.03.002
Persistent Legionella contamination of water faucets in a tertiary hospital in Japan.
Аннотация
OBJECTIVE
The feasibility of the decontamination procedure for Legionella pneumophila of water systems in healthcare facilities varies by water purification and disinfection methods in each country. We evaluated the efficacy of feasible decontamination strategies in Japan.
METHODS
This study was conducted at Tokyo Medical University Hospital (1015 beds) between 2015 and 2018. Samples from the water system and cooling tower were cultured periodically. Hyper-chlorination of cool tap water (>0.2 ppm), increases in the temperature of hot water (>55 °C), and flushing were used as decontamination strategies. The case of healthcare-associated legionellosis was surveyed. Environmental and clinical isolates were genotyped.
RESULTS
1439 environmental samples were collected; 19 (1.3%) samples tested positive for L. pneumophila from water faucets of patient rooms, toilets, waste rooms, and water sourced from wells. Genotyping of 12 isolates confirmed that the same strains were present in eight environmental isolates and two isolates from patients over three years. Although the environmental contamination of the water system was persistent, the number of positive locations of hospital environments gradually decreased; eight in 2015, four in 2016, three in 2017, and four in 2018, respectively.
CONCLUSIONS
Monitoring contamination, hyper-chlorination, controlling temperature, and flushing were effective as a Legionella decontamination strategy.
Предметные рубрики MeSH
Подготовка и перевод публикации
Обработка статьи · этапы, ошибки и управление
Ошибки и ограничения
История · было → стало
Состояние обновляется каждые 5 секунд, пока блок открыт. Процент показывается только там, где известен объём работы. Пауза останавливает продолжение этапа; текущий запрос к источнику может завершиться.
Тип публикации указан по данным источника. Уровень доказательности автоматически не присваивается.