Медицинская библиотека · American journal of infection control · 2019

Controlling Legionella pneumophila in water systems at reduced hot water temperatures with copper and silver ionization.

Cloutman-Green Elaine, Barbosa Vera L, Jimenez Diego, Wong Daniel, Dunn Helen, Needham Brian, Ciric Lena, Hartley John C

СтатьяПоддержка исследования: вне правительства СШАПеревод в очереди

Аннотация

BACKGROUND

Hospital-acquired Legionnaires' disease is associated with the presence of Legionella pneumophila in hospital water systems. In the United Kingdom, the Department of Health recommends maintaining hot water temperatures >55°C and cold water temperatures <20°C at the point of delivery to prevent proliferation of L pneumophila in water systems. In this study, we evaluated the efficacy of copper and silver ionization to control L pneumophila at deliberately reduced hot water temperatures (43°C) within a newly installed water system in a new building linked to a large health care facility in the United Kingdom.

METHODS

One thousand, five hundred ninety-eight water samples were collected between September 2011 and June 2017. Samples were tested using accredited methods for L pneumophila, copper and silver ion levels, and total viable counts. Energy consumption and water usage data were also collected to permit carbon emission calculations.

RESULTS

The results of 1,598 routine samples from September 2011 to June 2017, and the recordings of temperatures at outlets in this facility, demonstrated effective (100%) L pneumophila control throughout the study period with an average hot water temperature of 42°C. The energy savings and reduction of carbon emissions were calculated to amount to 33% and 24%, respectively, compared to an equivalent temperature-controlled system. Water system management interventions were required to achieve consistently adequate levels of copper and silver across outlets.

CONCLUSIONS

This study demonstrated that it is possible to control L pneumophila independent of temperature when copper and silver ionization is introduced into a new building in conjunction with an appropriately managed water system.

Для цитирования: Cloutman-Green Elaine, Barbosa Vera L, Jimenez Diego, Wong Daniel, Dunn Helen, Needham Brian, Ciric Lena, Hartley John C. Controlling Legionella pneumophila in water systems at reduced hot water temperatures with copper and silver ionization.. American journal of infection control. 2019. DOI: 10.1016/j.ajic.2018.12.005.

Предметные рубрики MeSH

Подготовка и перевод публикации
Обработка статьи · этапы, ошибки и управление
Загрузка состояния…

История · было → стало

Состояние обновляется каждые 5 секунд, пока блок открыт. Процент показывается только там, где известен объём работы. Пауза останавливает продолжение этапа; текущий запрос к источнику может завершиться.

Тип публикации указан по данным источника. Уровень доказательности автоматически не присваивается.