Energy Conservation and the Promotion of Legionella pneumophila Growth: The Probable Role of Heat Exchangers in a Nosocomial Outbreak.

Bédard Emilie, Lévesque Simon, Martin Philippe, Pinsonneault Linda, Paranjape Kiran, Lalancette Cindy, Dolcé Charles-Éric, Villion Manuela, Valiquette Louis, Faucher Sébastien P, Prévost Michèle

СтатьяПоддержка исследования: вне правительства СШАПеревод в очереди

Аннотация

OBJECTIVE To determine the source of a Legionella pneumophila serogroup 5 nosocomial outbreak and the role of the heat exchanger installed on the hot water system within the previous year. SETTING A 400-bed tertiary care university hospital in Sherbrooke, Canada. METHODS Hot water samples were collected and cultured for L. pneumophila from 25 taps (baths and sinks) within wing A and 9 taps in wing B. Biofilm (5) and 2 L water samples (3) were collected within the heat exchangers for L. pneumophila culture and detection of protists. Sequence-based typing was performed on strain DNA extracts and pulsed-field gel electrophoresis patterns were analyzed. RESULTS Following 2 cases of hospital-acquired legionellosis, the hot water system investigation revealed a large proportion of L. pneumophila serogroup 5 positive taps (22/25 in wing A and 5/9 in wing B). High positivity was also detected in the heat exchanger of wing A in water samples (3/3) and swabs from the heat exchanger (4/5). The outbreak genotyping investigation identified the hot water system as the source of infections. Genotyping results revealed that all isolated environmental strains harbored the same related pulsed-field gel electrophoresis pattern and sequence-based type. CONCLUSIONS Two cases of hospital-acquired legionellosis occurred in the year following the installation of a heat exchanger to preheat hospital hot water. No cases were reported previously, although the same L. pneumophila strain was isolated from the hot water system in 1995. The heat exchanger promoted L. pneumophila growth and may have contributed to confirmed clinical cases. Infect. Control Hosp. Epidemiol. 2016;1475-1480.

Для цитирования: Bédard Emilie, Lévesque Simon, Martin Philippe, Pinsonneault Linda, Paranjape Kiran, Lalancette Cindy, Dolcé Charles-Éric, Villion Manuela, Valiquette Louis, Faucher Sébastien P, Prévost Michèle. Energy Conservation and the Promotion of Legionella pneumophila Growth: The Probable Role of Heat Exchangers in a Nosocomial Outbreak.. Infection control and hospital epidemiology. 2016. DOI: 10.1017/ice.2016.205.

Предметные рубрики MeSH

Подготовка и перевод публикации
Обработка статьи · этапы, ошибки и управление
Загрузка состояния…

История · было → стало

Состояние обновляется каждые 5 секунд, пока блок открыт. Процент показывается только там, где известен объём работы. Пауза останавливает продолжение этапа; текущий запрос к источнику может завершиться.

Тип публикации указан по данным источника. Уровень доказательности автоматически не присваивается.