Thermal disinfection of hotels, hospitals, and athletic venues hot water distribution systems contaminated by Legionella species.

Mouchtouri Varvara, Velonakis Emmanuel, Hadjichristodoulou Christos

Оценочное исследованиеСтатьяПоддержка исследования: вне правительства СШАПеревод в очереди

Аннотация

Legionella spp. (> or = 500 cfu liter(-1)) were detected in 92 of 497 water distribution systems (WDS) examined. Thermal disinfection was applied at 33 WDS. After the first and second application of the disinfection procedure, 15 (45.4%) and 3 (9%) positive for remedial actions WDS were found, respectively. Legionella pneumophila was more resistant to thermal disinfection than Legionella non-pneumophila spp. (relative risk [RR]=5.4, 95% confidence intervals [CI]=1-35). WDS of hotels with oil heater were more easily disinfected than those with electrical or solar heater (RR=0.4 95% CI=0.2-0.8). Thermal disinfection seems not to be efficient enough to eliminate legionellae, unless repeatedly applied and in combination with extended heat flushing, and faucets chlorine disinfection.

Для цитирования: Mouchtouri Varvara, Velonakis Emmanuel, Hadjichristodoulou Christos. Thermal disinfection of hotels, hospitals, and athletic venues hot water distribution systems contaminated by Legionella species.. American journal of infection control. 2007. DOI: 10.1016/j.ajic.2007.01.002.

Предметные рубрики MeSH