Investigation and control of a cluster of cases of Legionnaires disease in western Sydney.

Brown J, Hort K, Bouwman R, Capon A, Bansal N, Goldthorpe I, Chant K, Vemulpad S

СтатьяПеревод в очереди

Аннотация

Three cases of Legionella pneumophila infection were identified in Sydney's west in November 1998. Epidemiological investigations identified an association with one workplace. Environmental sampling revealed that the cooling towers in the workplace, and at 2 other premises within a 1 km radius of the workplace, were positive for L. pneumophila serogroup 1 (LP1) which was indistinguishable from clinical isolates of 2 of the cases on DNA fingerprinting. Our report highlights limitations of the current control program for Legionella in cooling towers, including the finding of unregistered cooling towers, cooling towers positive for LP1 despite satisfactory results on inspection, and cooling towers potentially linked to disease with counts of LP1 below the current protocol requirements for immediate decontamination.

Для цитирования: Brown J, Hort K, Bouwman R, Capon A, Bansal N, Goldthorpe I, Chant K, Vemulpad S. Investigation and control of a cluster of cases of Legionnaires disease in western Sydney.. Communicable diseases intelligence quarterly report. 2001. DOI: 10.33321/cdi.2001.25.13.

Предметные рубрики MeSH

Подготовка и перевод публикации
Обработка статьи · этапы, ошибки и управление
Загрузка состояния…

История · было → стало

Состояние обновляется каждые 5 секунд, пока блок открыт. Процент показывается только там, где известен объём работы. Пауза останавливает продолжение этапа; текущий запрос к источнику может завершиться.

Тип публикации указан по данным источника. Уровень доказательности автоматически не присваивается.