Maintenance of cooling towers following two outbreaks of Legionnaires' disease in a city.

Bhopal R S, Barr G

СтатьяПоддержка исследования: вне правительства СШАПеревод в очереди

Аннотация

This survey assessed the maintenance of evaporative cooling towers in Glasgow, following two Legionnaires' disease outbreaks. Information was obtained from 76 of 81 premises and a maintenance score was calculated for each of 174 towers. The quality of maintenance was extremely varied (range of maintenance scores, 8-30; mean, 22 (S.D., 5.0); median, 23; maximum possible, 33) and some towers were neglected. Breaches of maintenance principles were mainly structural and organizational, e.g. inadequate drift control, rather than failure to use chemicals. Low maintenance scores were associated with no log book, no guidelines, no change in procedures in last 5 years, solitary cooling towers, and towers on industrial premises. Despite intense publicity the standard of cooling tower maintenance in Glasgow remained a concern. Information campaigns directed at those responsible for cooling-tower maintenance are necessary.

Для цитирования: Bhopal R S, Barr G. Maintenance of cooling towers following two outbreaks of Legionnaires' disease in a city.. Epidemiology and infection. 1990. DOI: 10.1017/s0950268800054492.

Предметные рубрики MeSH

Подготовка и перевод публикации
Обработка статьи · этапы, ошибки и управление
Загрузка состояния…

История · было → стало

Состояние обновляется каждые 5 секунд, пока блок открыт. Процент показывается только там, где известен объём работы. Пауза останавливает продолжение этапа; текущий запрос к источнику может завершиться.

Тип публикации указан по данным источника. Уровень доказательности автоматически не присваивается.