Role of hot water temperature and water system use on Legionella control in a tertiary hospital: An 8-year longitudinal study.
СтатьяНазвание и аннотация: Перевод в очереди
Обработка статьи · этапы, ошибки и управление
Загрузка состояния…
Ошибки и ограничения
История · было → стало
Состояние обновляется каждые 5 секунд, пока блок открыт. Процент показывается только там, где известен объём работы. Пауза останавливает продолжение этапа; текущий запрос к источнику может завершиться.
Gavaldà Laura, Garcia-Nuñez Marian, Quero Sara, Gutierrez-Milla Carmen, Sabrià Miquel
Аннотация
Although measures to minimize Legionella colonization in sanitary hot water installations are well established, there is little evidence of their long-term effectiveness in hospital buildings. During an 8-year period, hot water in a large hospital building was sampled monthly in areas with suitable dimensioning and recirculation and in areas with dead legs and low-use taps. In the former areas, the percentage of Legionella-negative samples was 83.2% when the temperature was ≥55%, 64.9% when between 50.1 °C and 54.0 °C, and 51.6% when ≤50 °C (p for trend <0.001). In the highest temperature group, no samples with ≥103 cfu/L were observed. In poorly designed areas, only 44.7% of samples were negative, and 28.9% presented ≥103 cfu/L although reaching 55 °C. In these areas, multivariate analysis showed that if hot water supplies were not used daily, the risk of Legionella colonization was greater than two-fold (odds ratio: 2.84; 95% confidence interval: 1.26-6.41), and the risk of finding Legionella concentrations ≥103 cfu/L was more than three-fold (odds ratio: 3.18; 95% confidence interval: 1.36-7.46), regardless the temperature. These findings indicate that the effectiveness of maintaining sanitary hot water at a minimum temperature of 55 °C is significantly better than that at 50 °C for the environmental control of Legionella but only in installations with suitable dimensioning and recirculation. In installations that do not meet these conditions, high temperatures alone result in insufficient control.