[Evaluation of reports on environmental measurements of electromagnetic fields generated by high voltage transmission lines and substations].
Аннотация
This paper presents some situations, in which measurements of electromagnetic fields generated by transmission lines and substations should be performed. The range of measurements may differ, but maximum values of electric and magnetic fields and flux density must be identified in all situations. The area with electric field exceeding 1 kV/m should be identified as well. The author also presents basic requirements to be met by the measurement technique. These requirements are specified according to the national standard. Special attention should be paid to the identification of the spatial distribution of electric field and flux density generated in the vicinity of high voltage transmission lines. To verify the measurement results, it is necessary to calculate the distribution of both aforesaid field components. For environmental protection purposes, it is also proposed that the report should include measurements of electromagnetic fields of 50 Hz along with calculated results presented in tables and diagrams.