Post-occupancy evaluation on temporary negative pressure isolation wards with portable high-efficiency particulate air filter units used during the COVID-19 pandemic in South Korea.

Lee Se Jin, Lee Won Seok, Roh Joo Yeon, Lee Shin Hye, Kim Eun Seok, Yeo Myoung Souk

СтатьяПоддержка исследования: вне правительства СШАПеревод пока не подготовлен

Аннотация

BACKGROUND

During the COVID-19 pandemic, in South Korea, several inpatient wards were converted to temporary negative pressure isolation (TNPI) wards by using portable high-efficiency particulate air filter units (PHUs). This study proposes improvements to the TNPI ward to prepare for airborne infections.

METHODS

Existing air-conditioning systems were investigated during the pandemic in 4 hospitals through a document review and field investigation with staff interviews. On-site experiments and measurements were conducted under vacant conditions. Differential pressure (∆P) between spaces was measured in all 4 hospitals, while tracer gas tests were carried out in 2 hospitals.

RESULTS

The investigation revealed that thermal discomfort caused the existing systems remaining perpetually active. Additionally, the noise generated by the PHU caused an unexpected shutdown of that equipment. Furthermore, the ∆P of over -2.5 Pa was measured as a result of the operating status of equipment. These situations can cause duct backflow and gas diffusion through unsealed diffusers. Moreover, low airtightness of existing facilities can affect indoor environment, pressure difference, and gas diffusion.

CONCLUSIONS

When using existing facilities as TNPI wards, the airtightness and existing systems should be considered. We concluded that it is important to increase the airtightness and seal unused diffusers in order to prevent cross-infection by unpredictable airflow.

Для цитирования: Lee Se Jin, Lee Won Seok, Roh Joo Yeon, Lee Shin Hye, Kim Eun Seok, Yeo Myoung Souk. Post-occupancy evaluation on temporary negative pressure isolation wards with portable high-efficiency particulate air filter units used during the COVID-19 pandemic in South Korea.. American journal of infection control. 2024. DOI: 10.1016/j.ajic.2024.08.025.

Предметные рубрики MeSH

Подготовка и перевод публикации
Обработка статьи · этапы, ошибки и управление
Загрузка состояния…

История · было → стало

Состояние обновляется каждые 5 секунд, пока блок открыт. Процент показывается только там, где известен объём работы. Пауза останавливает продолжение этапа; текущий запрос к источнику может завершиться.

Тип публикации указан по данным источника. Уровень доказательности автоматически не присваивается.