Aerosol Concentrations During Otolaryngology Procedures in a Negative Pressure Isolation Room.

Seresirikachorn Kachorn, Sirinara Patthrarawalai, Tangjaturonrasme Napadon, Panyametheekul Sirima, Ngamsritrakul Thawat, Supaphan Uraiwan, Boonroung Thirayu, Ongphichetmetha Napassorn, Koosrivinij Saraporn, Snidvongs Kornkiat

СтатьяПеревод пока не подготовлен

Аннотация

OBJECTIVE

To evaluate the role of a negative pressure room with a high-efficiency particulate air (HEPA) filtration system on reducing aerosol exposure in common otolaryngology procedures.

STUDY

DESIGN

Prospective quantification of aerosol generation.

SETTINGS: Tertiary care.

METHODS

The particle concentrations were measured at various times during tracheostomy tube changes with tracheostomy suctioning, nasal endoscopy with suctioning, and fiberoptic laryngoscopy (FOL), which included 5 times per procedure in a negative pressure isolation room with a HEPA filter and additional 5 times in a nonpressure-controlled room without a HEPA filter. The particle concentrations were measured from the baseline, during the procedure, and continued until 30 minutes after the procedure ended. The particle concentrations were compared to the baseline concentrations.

RESULTS

The particle concentration significantly increased from the baseline during tracheostomy tube changes (mean difference [MD] 0.80 × 106  p/m3 , p = .01), tracheostomy suctioning (MD 0.78 × 106  p/m3 , p = .004), at 2 minutes (MD 1.29 × 106  p/m3 , p = .01), and 3 minutes (MD 1.3 × 106  p/m3 , p = .004) after suctioning. There were no significant differences in the mean particle concentrations among various time points during nasal endoscopy with suctioning and FOL neither in isolation nor nonpressure-controlled rooms.

CONCLUSION

A negative pressure isolation room with a HEPA filter was revealed to be safe for medical personnel inside and outside the room. Tracheostomy tube change with tracheostomy suctioning required an isolation room because this procedure generated aerosol, while nasal endoscopy with suctioning and FOL did not. Aerosol generated in an isolation room was diminished to the baseline after 4 minutes.

Для цитирования: Seresirikachorn Kachorn, Sirinara Patthrarawalai, Tangjaturonrasme Napadon, Panyametheekul Sirima, Ngamsritrakul Thawat, Supaphan Uraiwan, Boonroung Thirayu, Ongphichetmetha Napassorn, Koosrivinij Saraporn, Snidvongs Kornkiat. Aerosol Concentrations During Otolaryngology Procedures in a Negative Pressure Isolation Room.. Otolaryngology--head and neck surgery : official journal of American Academy of Otolaryngology-Head and Neck Surgery. 2023. DOI: 10.1002/ohn.177.

Предметные рубрики MeSH

Подготовка и перевод публикации
Обработка статьи · этапы, ошибки и управление
Загрузка состояния…

История · было → стало

Состояние обновляется каждые 5 секунд, пока блок открыт. Процент показывается только там, где известен объём работы. Пауза останавливает продолжение этапа; текущий запрос к источнику может завершиться.

Тип публикации указан по данным источника. Уровень доказательности автоматически не присваивается.