Revista espanola de anestesiologia y reanimacion · 1995

[Failure of the central oxygen supply to a surgical area. Analysis of a critical incident].

СтатьяНазвание и аннотация: Перевод пока не подготовлен
Обработка статьи · этапы, ошибки и управление
Загрузка состояния…

История · было → стало

Состояние обновляется каждые 5 секунд, пока блок открыт. Процент показывается только там, где известен объём работы. Пауза останавливает продолжение этапа; текущий запрос к источнику может завершиться.

Herrera A, Bueno F

Аннотация

An incident involving central oxygen supply failure affecting 4 anesthetized patients in the operating theatre was analyzed by way of interviews with the anesthesiologists and a review of graphic records of anesthesia. The 4 ventilators involved had been checked by each anesthesiologist according to his own method. The oxygen supply failure alarm warned of the supply cutoff in 2 cases and the oxygen analyzer detected the other 2 within approximately 1 minute. After the failure, 2 patients were ventilated with ambient air through the ventilator, 1 was given medicinal air with the resuscitator. None suffered damage or recalled having awakened as a result of the incident. The cause of the failure in oxygen supply has not been determined but its duration has been estimated to be between 4 and 7 minutes. Our investigation shows that: 1) the operating rooms are not equipped with an alarm that warns of a drop in pressure within the tubes that supply central oxygen and in 2 cases the alarm warning of a cutoff in oxygen supply to the respirator did not sound correctly; 2) the ventilator equipment check did not follow a standard method and did not cover the possibility of oxygen supply failure, and 3) no alternative oxygen supply is available inside the operating theatre.(ABSTRACT TRUNCATED AT 250 WORDS)

Предметные рубрики MeSH

ИП Урсолов Владлен Сергеевич

ИНН 500118482352 · ОГРНИП 314500117700049

Реквизиты и контакты