Measurement of the magnetic fields of high-voltage substations (230 kV) in Tehran (Iran) and comparison with the ACGIH threshold limit values.

Fard Mahdieh Sharifi, Nasiri Parvin, Monazzam Mohammad Reza

Сравнительное исследованиеСтатьяПеревод пока не подготовлен

Аннотация

Measurements were made according to IEEE standard 644-1994 at a height of 1 m above floor level. It is concluded that none of the measurements exceeded the ACGIH threshold limit value. Among all control rooms the highest measured density amount is 0.69 μT in the control room of Ozgol substation and the lowest is 0.2 μT in the post of Shahid Firouzi. The control room of Ozgol substation is located in the second floor and bus-bars are located at a short distance from the window on the east, and so the highest recorded magnetic field is measured in this control room. Among all switchgear parts the highest amount 9.15 μT is measured in Kan substation. None of the measurements exceeded the ACGIH threshold limit value.

Для цитирования: Fard Mahdieh Sharifi, Nasiri Parvin, Monazzam Mohammad Reza. Measurement of the magnetic fields of high-voltage substations (230 kV) in Tehran (Iran) and comparison with the ACGIH threshold limit values.. Radiation protection dosimetry. 2010. DOI: 10.1093/rpd/ncq445.

Предметные рубрики MeSH

Подготовка и перевод публикации
Обработка статьи · этапы, ошибки и управление
Загрузка состояния…

История · было → стало

Состояние обновляется каждые 5 секунд, пока блок открыт. Процент показывается только там, где известен объём работы. Пауза останавливает продолжение этапа; текущий запрос к источнику может завершиться.

Тип публикации указан по данным источника. Уровень доказательности автоматически не присваивается.