Rapid on-site monitoring of Legionella pneumophila in cooling tower water using a portable microfluidic system.

Yamaguchi Nobuyasu, Tokunaga Yusuke, Goto Satoko, Fujii Yudai, Banno Fumiya, Edagawa Akiko

СтатьяПоддержка исследования: вне правительства СШАПеревод в очереди

Аннотация

Legionnaires' disease, predominantly caused by the bacterium Legionella pneumophila, has increased in prevalence worldwide. The most common mode of transmission of Legionella is inhalation of contaminated aerosols, such as those generated by cooling towers. Simple, rapid and accurate methods to enumerate L. pneumophila are required to prevent the spread of this organism. Here, we applied a microfluidic device for on-chip fluorescent staining and semi-automated counting of L. pneumophila in cooling tower water. We also constructed a portable system for rapid on-site monitoring and used it to enumerate target bacterial cells rapidly flowing in the microchannel. A fluorescently-labelled polyclonal antibody was used for the selective detection of L. pneumophila serogroup 1 in the samples. The counts of L. pneumophila in cooling tower water obtained using the system and fluorescence microscopy were similar. The detection limit of the system was 104 cells/ml, but lower numbers of L. pneumophila cells (101 to 103 cells/ml) could be detected following concentration of 0.5-3 L of the water sample by filtration. Our technique is rapid to perform (1.5 h), semi-automated (on-chip staining and counting), and portable for on-site measurement, and it may therefore be effective in the initial screening of Legionella contamination in freshwater.

Для цитирования: Yamaguchi Nobuyasu, Tokunaga Yusuke, Goto Satoko, Fujii Yudai, Banno Fumiya, Edagawa Akiko. Rapid on-site monitoring of Legionella pneumophila in cooling tower water using a portable microfluidic system.. Scientific reports. 2017. DOI: 10.1038/s41598-017-03293-9.

Предметные рубрики MeSH

Подготовка и перевод публикации
Обработка статьи · этапы, ошибки и управление
Загрузка состояния…

История · было → стало

Состояние обновляется каждые 5 секунд, пока блок открыт. Процент показывается только там, где известен объём работы. Пауза останавливает продолжение этапа; текущий запрос к источнику может завершиться.

Тип публикации указан по данным источника. Уровень доказательности автоматически не присваивается.